Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T17CM03451
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2017 | PIMA COUNTY | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T17CM03451- PERMIT REVIEW COMMENTS BUILDING- Residential Reviewer: Larry Chavez, June 13, 2017 GENERAL Provide Manual J mechanical load calcs showing how the house conforms to the requirements of the IRC. SHEET A1 Show the finished floor elevation for each structure relative to the highest adjacent grade next to the structure. Where decks are more than 30” above grade & more than 200 SF in area, provide guards as required by R312. Where more than 4 risers are provided, provide handrails per R311.7 Show the conduit and conductors going from the Main Panel to Panel B. SHEET A2 Where decks are more than 30” above grade & more than 200 SF in area, provide guards as required by R312. Where more than 4 risers are provided, provide handrails per R311.7 Provide a note indicating the insulation R-value for walls, the U-factor of 0.40 for glass and an SHGC of 0.25. SHEET A6 In the sections, callout floor insulation R-value of at least R-13. Call out wall and roof insulation as required by Chapter 11 or the IRC. SHEET E1 Provide an electrical load calc per Table E3602.2 that includes electrical for the mechanical equipment and for the tankless water heater in the studio. Show the mechanical equipment in the panel schedule in the appropriate circuit space. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/26/2017 | MMENDIB1 | OUT TO CUSTOMER | Completed |