Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/04/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise detail 5/p3.0 to reflect the separate indirect waste pipes at the ice machine. [Initial comment: Provide separate indirect waste pipes for each drain from the ice cuber and ice bin to protect against cross-contamination or fouling (detail 5/P3.0). Reference: Section 801.2, IPC 2012.] 2. An approval from RWRD is required to eliminate the connection of the mop sink to the grease interceptor. Reference: Section 1003.3, IPC 2012 as amended by the City Of Tucson. |
05/11/2017 | KROBLES1 | WWM | REVIEW | Needs Review |