Permit Number: T17CM03077
Parcel: 117050400

Address:
429 N 4TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM03077
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise detail 5/p3.0 to reflect the separate indirect waste pipes at the ice machine. [Initial comment: Provide separate indirect waste pipes for each drain from the ice cuber and ice bin to protect against cross-contamination or fouling (detail 5/P3.0). Reference: Section 801.2, IPC 2012.]
2. An approval from RWRD is required to eliminate the connection of the mop sink to the grease interceptor. Reference: Section 1003.3, IPC 2012 as amended by the City Of Tucson.
05/11/2017 KROBLES1 WWM REVIEW Needs Review