Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM03077
Parcel: 117050400

Address:
429 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM03077
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2017 ANDREW CONNOR ZONING REVIEW Approved
04/20/2017 MARTIN BROWN FIRE REVIEW Reqs Change Please provide acrhitectural stamps.
Ariel views from google maps indicate potential problems with egress from west side of property. Please show what is happening once people leave patio.
The patio should have an occupant load. Please clarify.
04/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide registrant stamp on the plans. Otherwise the electrical is approved.
04/20/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/20/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet a0.2; Exiting Plan: It appears there is a patio space on the left end of the building. Is this a dining area? If so, the area of the patio should be included in the total gross building area, in addition to adding occupants to the total load.
2. Sheet a3.0; Floor Plan Key Notes: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
3. Sheet a3.0; Key Plan: If the total occupant load is revised, please verify the required number for accessible seating meets the Code requirement.
4. Sheet a3.0 (Key Plan); Sheet a5.1 (Door Schedule): The door schedule does not list door 111b (at the patio). Please verify.
5. General: Per the IBC Section 3411.7, up to 20% of the project cost must be applied to accessibility issues. Please indicate on the drawings what accessible issue is part of that requirement (grab bars, accessibility into building, accessibility in building, etc.?).
6. General: Please provide north arrows on all plans.
7. General: Please provide professional stamps on all sheets.
8. General: Please provide written responses to all review comments.
04/21/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the mechanical drawings to clearly show the intended scope of work for this activity. Sheet M1.0 states that all mechanical equipment is existing but the key notes for the mechanical plan call for a new rooftop AC unit and a new exhaust fan. Fan coil FC-1 is noted as existing but it is not shown; show the unit and outside air duct for the unit.
04/21/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
04/21/2017 PAUL BAUGHMAN ENGINEERING REVIEW Passed
04/21/2017 ROBERT SHERRY WATER REVIEW Completed
04/25/2017 GERRY KOZIOL WWM REVIEW Needs Review