Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM02816
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/02/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G-101: The drawing index does not match the submitted sheets (P-301). Please revise. 2. Sheet D-101; Demolition Floor Plan: Is it possible to remove the entire piece of wall in the women's restroom (Key Note 4) to make this restroom compliant with the ICC/ANSI Figure 604.3? Please verify. 3. Sheet A101; Keynotes: Note 5 is mididentified. Please revise. 4. Sheet A-101; Floor Plan 3: Please indicate on the drawings how the new walls at the stairs are anchored at the base, and how they are braced at the top of the wall. Please include bracing size, spacing, anchorage to the wall, and anchorage to the structure above. 5. Sheet A-101; Floor Plan 3: Please provide on the drawings the handrail requirements for the stair to the loft. Verify those handrails used meet the requirements of the IBC Section 1012. 6. Sheet A-102; Key Notes and General Notes: Please indicate on the drawings how the new walls indicated in Key Notes 1, 2, and 3 and General Note 4 are anchored at the base, and how they are braced at the top of the wall. Please include bracing size, spacing, anchorage to the wall, and anchorage to the structure above. 7. Sheet A-102; Key Notes: Please indicate on the drawings how the new wall indicated in Key Note 8 is anchored at the base, and how it is braced at the top of the wall. Please include bracing size, spacing, anchorage to the wall, and anchorage to the structure above as required. 8. Sheet A-103; Elevations 2B and 3B (Key Note 6): Please revise the vertical grab bar length to 18" per the ICC/ANSI Figure 604.5.1. 9. Sheet A-103; Elevations 2A, 2B, 3A, and 3B: Please locate the horizontal grab bars per the ICC/ANSI Figure 604.5.1 and 604.5.2. 10. General: Please indicate on the drawings the requirements of the ICC/ANSI Chapter 7 are met for restroom signage. 11. General: Please provide written responses to all review comments. |
05/02/2017 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Verify the size of the existing water meter serving this address, its serial number, and the total demand served by the meter. 2. Provide the size of the reduced pressure backflow prevention assembly serving this suite. Reference: Section 107.2.1, IBC 2012. |
05/02/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Air admittance valves are not approved for use in a combination drain and vent system. Reference: Section 918.3, IPC 2012. |
05/02/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the quantity of general room exhaust for the kitchen. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance (two convection ovens and one microwave oven). Reference: Sections 403.3 and 507.2.2, IMC 2012. 2. Provide general exhaust for the kitchen continuously during the occupied hours. Reference: Section 403.3, IMC 2012. |
05/10/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |