Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM02636
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S3.3 (Section 106); Structural Calculations (Sheets 23 through 30): The calculations provide sizes and details for the shoring of the pit wall shown in Section 106/S3.3. However, that detail (Note 8) indicates shoring but provides no sizes or details. Please include the information in the calculations on the drawings. Please verify. 2. Sheet S3.11 (Detail 253); Structural Calculations (Sheet 58): The metal wall studs per the calculations are indicated on Detail 253/S3.11. Is there a note or a reference on any of the plans or schedules as to the size of these wall studs? Please provide a reference on the plans for this condition. Is there a chance this will be indicated on the architectural plans (not included in this submittal)? Details 255 and 256 on Sheet S3.11 do indicate connection details, but do not indicate a stud size. 3. General: Please provide written responses to all review comments. |