Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2017 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change Approval of DP17-0052 is required first.
04/12/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: 1151 E. Hermans Road
T17CM02633 & T17CM02634
Building Plan (1st Review)

TRANSMITTAL DATE: April 12, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until development package DP17-0052 is fully approved the building plans cannot be approved.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/14/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM02633 –PLAN REVIEW COMMENTS
BUILDING – COMMERCIAL
Reviewer: Chris Anderson, April 13, 2017

A note on sheet S1.0 says “See architectural and mechanical drawings for dimensioned locations of walls, columns and concrete slab edges.” There are no architectural drawings in this submittal. Submit dimensioned plans and elevations of the CUP and control buildings. Also add a note that prefabricated building drawings and structural calculations to be submitted as a deferred submittal. Ref. 2012 IBC 107.2.1.
Means of egress per 2012 IBC Chapter 10 from each building has not been addressed in these drawings. Ref. 2012 IBC 107.2.1.
04/14/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Reviewer: Chris Anderson, April 13, 2017

Provide complete plumbing plans for the CUP and control room buildings for sanitary, venting and domestic water. Indicate pipe sizes, locations, plumbing fixtures schedule and connection details as appropriate, and fixture unit calculations. The plan(s) must match what is shown on the site utility plans (activity number T17CM02633). For example, the site utility plan indicates three sanitary lines exiting the CUP building.
04/14/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
Reviewer: Charlie Bard, April 13, 2017

On sheet E1.SB no general purpose or emergency/exiting light fixtures are shown in the electrical control room. Ref. 2011 NEC 110.33(D).
On sheet E3.SA no general purpose or emergency/exiting light fixtures are shown in the CUP building. Ref. 2011 NEC 110.33(D).
No lighting is shown for electrical vaults. Ref. 2011 NEC 110.33(D).
Provide electric plans for the vaults showing equipment layout and clearances per 2011 NEC 110.
04/14/2017 FRODRIG2 WATER REVIEW Reqs Change WATER – COMMERCIAL
Reviewer: Chris Anderson, April 13, 2017

Submit water calculations for CUP building and control building. 2012 IPC 106.3.1.
04/14/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
Reviewer: Chris Anderson, April 13, 2017

Provide load calculations summary sheets to justify capacities of the selected chiller system. Ref. 2012 IMC 106.3.1.
04/18/2017 MARTIN BROWN FIRE REVIEW Approved
04/25/2017 GERRY KOZIOL WWM REVIEW Reqs Change Reference only: for Site Utility Package under T17CM02634:

Need PCRWRD Type III Capacity review – PCRWRD/Kurt Stemm (Kurt.Stemm@pima.gov - 502-724-6607).

Need PSL review and approval – PCRWRD/Tom Porter (Thomas.porter@pima.gov – 520-724-6719).

Need PDEQ review and approval of private sewer with private sewer manhole (buildings #918, #919, #920, #921(with private lift station) and Control Building(No building #).

Rene Gomez – rene.gomez@pima.gov – 724-7365.

*This private sewer connects to an existing on-site private sewer.

Need email/electronic pdf of Private Sewer Drawing C1.USSA, #C1.USS1, C1.USS2, C1.USS3 and C1USS4 for Map Guide update.

*Please include utility plan drawings C1.UA and C1.U01 thru C1.U12 for reference.

Needs Public Sewer Construction Permit for building #922 (C1.U01) - 4” private HCS to existing 8” public sewer per drawing C1.U01

*only if COT will not inspect this connection.

PCRWRD - Sylvia.Quinlan@pima.gov (520-724-6649)

Need to submit site/plumbing drawings for PCRWRD/Industrial Wastewater Control review(IWC) – Steven.Valencia@pima.gov (520-724-6200).

*Includes building #921 with private lift station and building #919 - Central Utility Plant (chilled water).


Future needs: (for future building sewer connection fee calculation):

Need clarification of all new domestic building water meters that are being proposed with water supply fixture units.

*It is noted for building #922 – one new 1-1/2” COT water meter is proposed.

*Water supplied from wells need to be clearly identified on drawings with WSFU’S if applicable.

*The Civil Site Package under #T17CM02634 needs to be approved prior to the building permit (Central Utility Plant – building #919) under #T17CM02633 is approved.

Need to submit site/plumbing drawings for PCRWRD/Industrial Wastewater Control review(IWC) – Steven.Valencia@pima.gov (520-724-6200).

*Building #919 - Central Utility Plant (chilled water).

Need clarification of all new domestic building water meters that are being proposed with water supply fixture units for sewer connection fee calculation.

*Water supplied from wells need to be clearly identified on drawings with WSFU’S if applicable.

Need PCRWRD Type III Capacity review – PCRWRD/Kurt Stemm (Kurt.Stemm@pima.gov - 502-724-6607).

*Could be handled in site review.
04/25/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/15/2017 ARUIZ1 OUT TO CUSTOMER Completed