Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T17CM02528
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/11/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 04/20/2017 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL – COMMERCIAL Submit lumen calculations for the entire parcel showing compliance with Table 401.1 of the City of Tucson/Pima County Outdoor Lighting Code and additional requirements of the OLC. The submitted lighting wattage COMcheck identified the square footage as 3,083 SF however the total area of the building is 6,446 square feet. Explain. |
| 04/20/2017 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING – COMMERCIAL On Plumbing Fixtures schedule, sheet M-2, confirm that selected lavatory faucets will deliver no more than .25 gallon per metering cycle per City of Tucson amendment to the 2012 IPC. Sheet U-1 does not show a sewer line for this building. Add to drawing and show connection point to existing. Provide a backflow preventer on the water service line. Show location on sheet U-1 |
| 04/20/2017 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T17CM02528 –PLAN REVIEW COMMENTS Reviewer: Chris Anderson, April 19, 2017 BUILDING – COMMERCIAL Store front is described out in the COMcheck envelope compliance report as thermally broken whereas the 08400 Aluminum Storefront specification does not require a TB frame. Edit the specification to comply with the COMcheck energy requirement. Add to 08400 Aluminum Storefront that for the storefront the maximum U-value shall be 0.33 and maximum SHGC shall be 0.27; and the maximum U-value for the entry doors shall be 0.330 and maximum SHGC shall be 0.27. This information is required so that the specification matches the COMcheck descriptions. Specification 08250 Overhead Rolling Door, 2.01(A) specifies an R-value of 7.2; however the envelope COMcheck specifies a minimum R-value of 8.5 (1/U-.117). Revise specification and specify a different door if necessary to comply with COMcheck. Specification 08100 HM Doors and Frames does not appear to include insulated exterior doors. Add exterior doors to specification with a note that maximum U-value for insulated exterior steel doors shall be 0.240. This information is required so that the specification matches the COMcheck descriptions. On sheet A-1.1, text in details 1 and 3 must be minimum 3/32” high (both upper and lower case) to comply with City of Tucson standard. The U-value and SHGC shown on detail 7/A-5 are incorrect. Change U-value to 0.33 and the SHGC to 0.27. |
| 04/20/2017 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principle Planner PROJECT: AutoZone - 10210 E. Golf Links Road T17CM02528 Building Plan (1st Review) TRANSMITTAL DATE: April 20, 2017 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. It appears that the building plans match the proposed development package DP17-0032 but until the development package has been approved Zoning cannot approve the foundation plan. 3. Ensure that all site details provided within the building plan match what are shown on the development package, i.e. bicycle rack dimensions, accessible sign mounting heights, etc. 4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 04/20/2017 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL Provide heating and cooling load calculations summary sheets to justify the capacity of selected equipment. Ref. 2012 IECC C403.2.1 and C403.2.2. Use 104-degrees F summer DB outdoor design temperature with 66-degrees F design wet bulb temperature, and 32-degrees F winter DB outside design temperature per City of Tucson amendment to the 2012 IECC. Per IECC C403.2.1 and C403.2.2 “the output capacity of heating and cooling equipment and systems shall not exceed the loads calculated in accordance with Section C403.2.1.” |
| 04/28/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/11/2017 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |