Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM02476
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 06/20/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/20/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Show circuit and panel designations for all mechanical, appliances, or other equipment on the electrical floor plans. #2. Provide a symbol or letter designation for each luminaire inside and outside the building that correlates with the luminaire schedule. #3. Provide complete Outdoor Lighting Code compliance. The information submitted on the plans should include ; Color temperature output, fully shielded, or non-shielded, Lumens allowed per acre, notation for special inspection. Please see section 104.2, Plan submission requirements. #4. Provide complete compliance with the 2012 IECC for the lighting. #5. 120 volt outlets need to be GFI protected per NEC 210.8 Ref: 2012 IBC ,2011NEC |
| 06/20/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 06/21/2017 | ARUIZ1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/21/2017 | ARUIZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | Need details for ADA restroom. As proposed, does not meet ADA requirements. |
| 06/21/2017 | ARUIZ1 | WWM | REVIEW | Needs Review | |
| 06/21/2017 | ARUIZ1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |