Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/20/2017 MARTIN BROWN FIRE REVIEW Approved
06/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Show circuit and panel designations for all mechanical, appliances, or other equipment on the electrical floor plans.
#2. Provide a symbol or letter designation for each luminaire inside and outside the building that correlates with the luminaire schedule.
#3. Provide complete Outdoor Lighting Code compliance. The information submitted on the plans should include ; Color temperature output, fully shielded, or non-shielded, Lumens allowed per acre, notation for special inspection. Please see section 104.2, Plan submission requirements.
#4. Provide complete compliance with the 2012 IECC for the lighting.
#5. 120 volt outlets need to be GFI protected per NEC 210.8
Ref: 2012 IBC ,2011NEC
06/20/2017 ANDREW CONNOR ZONING REVIEW Approved
06/21/2017 ARUIZ1 MECHANICAL-COMMERCIAL REVIEW Needs Review
06/21/2017 ARUIZ1 BUILDING-COMMERCIAL REVIEW Needs Review Need details for ADA restroom. As proposed, does not meet ADA requirements.
06/21/2017 ARUIZ1 WWM REVIEW Needs Review
06/21/2017 ARUIZ1 PLUMBING-COMMERCIAL REVIEW Needs Review