Permit Number: T17CM02466
Parcel: 13405118R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM02466
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/07/2017 GERRY KOZIOL WWM REVIEW Reqs Change The following is needed for Sewer Connection Fee Application Approval:



Need Type III Capacity from PCRWRD/Kurt Stemm – 520-724-6607 (Kurt .Stemm@pima.gov).



Need COT review and approval of 4” private sewer extension from 1040 S Harrison Road with joint sewer agreement.



Need to identify dental office suite # (east end), if this T.I. is to be included with the shell.





*Does not include the installation of the 1500 gallon grease interceptor with the shell per VVC Design.

(This will need PCRWRD/IWC/Steven Valencia’s review upon submission of the future restaurant T.I. at west end)

520-724-6200 ( Steven.valencia@pima.gov)



*Drawing P1.0 indicates a new 1-1/2” water meter. Fee: $27,030.00.
06/07/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed