Permit Number: T17CM02466
Parcel: 13405118R

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM02466
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved
05/15/2017 MARTIN BROWN FIRE REVIEW Approved
05/15/2017 DAVID RIVERA ZONING REVIEW Approved
05/25/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change TI: Dental Office

Where are the returns for rooms 106 ad 107? [Initial comment: Revise the mechanical design as required to avoid using the corridors as return air ducts (HP3 and HP4). Reference: Section 601.2, IMC 2012.]
05/25/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change TI: Dental Office

1. The keynotes on sheet TA-1 state that the air compressor is to be mounted on a 34" high shelf. [Initial comment: Provide structural calculations and details to show that the proposed air compressor will be safely supported. Reference: Section 1602.4, IBC 2012.]
2. Comment not addressed. [Initial comment: Provide maintenance access and operating space for the air compressor in accordance with the manufacturer's installation instructions. Reference: Sections 304.1 and 306.1, IMC 2012.]
05/25/2017 ROBERT SHERRY WATER REVIEW Completed
06/01/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/05/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/06/2017 GERRY KOZIOL WWM REVIEW Reqs Change The following is needed for Sewer Connection Fee Application Approval:

Need Type III Capacity from PCRWRD/Kurt Stemm – 520-724-6607 (Kurt .Stemm@pima.gov).

Need COT review and approval of 4” private sewer extension from 1040 S Harrison Road with joint sewer agreement.

Need to identify dental office suite # (east end), if this T.I. is to be included with the shell.

*Does not include the installation of the 1500 gallon grease interceptor with the shell per VVC Design.

(This will need PCRWRD/IWC/Steven Valencia’s review upon submission of the future restaurant T.I. at west end)

520-724-6200 ( Steven.valencia@pima.gov)

*Drawing P1.0 indicates a new 1-1/2” water meter. Fee: $27,030.00.