Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM02466
Parcel: 13405118R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02466
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2017 MARTIN BROWN FIRE REVIEW Reqs Change Please read the commentary for table 1018.1. It is my interpretation that the corridors need to be 1 hour rated.
Also, please indicate the type and quantity of medical gases in building.
04/11/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Shell:

1. Provide the size of the backflow preventer associated with the water meter. Reference: Section 107.2.1, IBC 2012.
2. Show the size and material of the water service pipe; revise the site plan as required to clearly show the route of the water service pipe.
3. Specify the materials of construction for the building sewer. Reference: Section 702, IPC 2012.
4. Provide roof drainage calculations and plans. Include the horizontal area of the coping and the effect of any vertical walls that can divert rainfall onto the roof. Reference: Sections 1101, 1106 and 1108, IPC 2012.
5. Show the size, slopes, routing, and termination points for the roof drain and overflow roof drain conductors. Note that the roof drain conductors and the overflow drain conductors are independent and shall have different termination points. Reference: Sections 1106 and 1108, IPC 2012.

TI: Dental Office

1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. drinking fountains and a service sink). Reference: Section 410.2, IPC 2012.
2. The data from Tucson water indicates a low water pressure of 49 PSI and a high water pressure of 56 PSI for this address. Evaluate the water pipe sizing calculations based on the low water pressure. Reference: Section 604.6, IPC 2012.
3. Revise the Energy Compliance notes on sheet P1.0 to recognize that the developed length of hot water pipe to the furthest outlet is over 50 feet (as depicted on the plumbing plan). Reference: Section 607.2, IPC 2012.
4. Revise detail F/P1.2 to clearly show the connection of the hot water recirculation pipe to the cold water inlet pipe to the water heater. Reference: Section 607.2.2, IPC 2012.
5. Explain keynote #3 on sheet P1.2 that calls for a water supply to the dental chairs while another note on the sheet states that the chairs are to have bottled water. Reference: Section 107.2.1, IBC 2012.
6. Clarify what appears to be a keynote #2 in detail F/P1.2. Reference: Section 107.2.1, IBC 2012.
7. Provide structural calculations and details to show that the proposed air compressor will be safely supported. Reference: Section 1602.4, IBC 2012.
8. Provide maintenance access and operating space for the air compressor in accordance with the manufacturer's installation instructions. Reference: Sections 304.1 and 306.1, IMC 2012.
9. Show that the compressed air distribution piping is specified in accordance with the conditions of the manufacturer's installation requirements for the air compressor. Reference: Section 304.1, IMC 2012.
04/12/2017 ROBERT SHERRY WATER REVIEW Reqs Change Show the locations of the water meter and reduced pressure backflow assembly that will be serving the new building.
04/13/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: 1060 S. Harrison Road
T17CM02466
Building Plan (1st Review)

TRANSMITTAL DATE: April 13, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/13/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Shell:

1. Revise the site plan to clearly show which building is being built with this activity. Reference: Section 107.2.1, IBC 2012.
2. Revise the energy code analysis for the building envelope, coordinating the building components used in the analysis with those shown on the drawing. Reference: Section C303.1, IECC 2012, as amended by the City of Tucson.
3. Clarify how the projection factors for the two types of fenestration was calculated. Re-calculate the area of each type of fenestration. Will the thermal performance specifications for the insulating glass (Section 08800, 4; Sheet A6) be changed to agree with the COMcheck values? Reference: Section 107.2.1, IBC 2012.
4. Provide NFRC-certified U-value and SHGC data for the solar tubes Reference: Section 107.2.1, IBC 2012.
5. Revise the roof details to indicate the presence of the continuous insulation. Reference: Section 107.2.1, IBC 2012.
6. Provide heating and cooling load calculations that justify the capacities of the two heat pumps specified for the shell space. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.

TI: Dental Suite

1. Provide heating and cooling load calculations that justify the capacities of the three heat pumps specified for the dental office. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
2. The ventilation calculations for the dental office show a minimum requirement of 904 CFM of outside air but the heat pump schedule calls for a total of only 800 CFM of outside air from the three heat pumps serving the space. Provide the required amount of outside air to the suite. Reference: Section 403.2, IMC 2012.
3. Clarify the route and termination point of the dryer exhaust. Keynote #6 calls for the vent to terminate at an exterior wall with a weather hood but the plans imply a termination at the roof. Reference: Section 107.2.1, IBC 2012.
4. Show where keynote #5 occurs. Reference: Section 107.2.1, IBC 2012.
5. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012.
6. Revise the mechanical design as required to avoid using the corridors as return air ducts (HP3 and HP4). Reference: Section 601.2, IMC 2012.
04/24/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet C1; Code Analysis: Please revise the accessibility code to the 2009 edition of the ICC/ANSI A117.1.
2. Sheet C1; Scope of Work: Please indicate on this sheet the square footage for the tenant improvement and the square footage for the remaining shell.
3. Sheet 1 of 8 (Site Plan); Sheet 2 of 8 (Site Plan): Sheet 1 indicates the proposed building on parcel 1 as 41,645 square feet. Sheet 2 indicates 6486 square feet for the same building. Please clarify.
4. Sheet A1; Key Notes: Notes 9 and 10 were not located on the plan. Please verify.
5. Sheet A1 (Wall Types); Sheet S2.0 (Foundation Plan Notes): Sheet A1 indicates exterior walls shall be 6" metal studs at 16" o.c.. Sheet S2.0 (note 9) indicates exterior walls shall be 6" steel studs at 12" o.c. Please coordinate.
6. Sheet A1 (Floor Plan); Sheet A4 (Door Schedule): The plan and door schedule indicate a door 100E, but under hardware group number 1 on A4, a note indicates only doors 100A, 100B, 100C, and 100D. Please coordinate.
7. Sheet A1 (Floor Plan); Sheet A4 (Hardware Group Number 2): A note indicates for use on door 101. Where is door 101 located on the plan? Please verify.
8. Sheet A2; Roof Plan: Per the IBC Section 1009.16.2, a roof hatch opening within ten feet of the roof edge must be protected by guards per Section 1013. Please verify and provide as required.
9. Sheet A3; Section Notes: Notes 2, 4, 21, 26, and 33 were not located on the elevations or sections. Please verify.
10. Sheet TA-1; Floor Plan: Per the IBC Table 2902.1, a drinking fountain is required. The City of Tucson allows a high/low drinking fountain, or a single point of use water dispenser (connects directly to a water line, but requires no drain), with cups at an accessible height. Please indicate on the drawing the fixture selected. In addition, the existing water cooler is located in the lounge. Will the public be allowed to use an approved drinking fountain or point of use dispenser in that location? Please verify.
11. Sheet TA-1.1; Elevation 2, Elevation 3, and the Snow Finish Schedule: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
12. Sheet TA-2; Detail 2, Elevation 16, and Detail 18: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
13. Sheet TA-3; Elevation 3: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
14. Sheet TH-1; Details 4, 7, 8, 11, and 17: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
15. Sheet TH-1; Plan Detail 4: Please locate the horizontal grab bar on the back wall per the ICC/ANSI Figure 604.5.2.
16. Lumishade Canopy: Please provide structural calculations for the canopies stamped by a licensed engineer. In addition, provide stamped drawings (minimum 11" x 17") for the canopies.
17. General: Please provide written responses to all review comments.
04/27/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/02/2017 GERRY KOZIOL WWM REVIEW Reqs Change The following is needed for Sewer Connection Fee Application Approval:

Need Type III Capacity from PCRWRD/Kurt Stemm – 520-724-6607 (Kurt .Stemm@pima.gov).

Need COT review and approval of 4” private sewer extension from 1040 S Harrison Road with joint sewer agreement.

Need to identify dental office suite # (east end), if this T.I. is to be included with the shell.

*Does not include the installation of the 1500 gallon grease interceptor with the shell per VVC Design.

(This will need PCRWRD/IWC/Steven Valencia’s review upon submission of the future restaurant T.I. at west end)

520-724-6200 ( Steven.valencia@pima.gov)

*Drawing P1.0 indicates a new 1-1/2” water meter. Fee: $27,030.00.