Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM02387
Parcel: 10602001C

Address:
3964 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM02387
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 3; SHEET A1.0; FLOOR PLAN; WALL TYPES: FOR THE NEW ONE HOUR FIRE RESISTANCE RATED WALL DESCRIPTION, PLEASE ADD THE U.L. LISTING NUMBER FOR THE 3 5/8" AND THE 6" STUD WALLS. THIS CAN BE INDICATED ON SECTION 4/A8.0.
05/31/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/31/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The structural detail for support of hood KH-1 shows the hood being horizontally-lagged to a wooden beam which does not comply with the manufacturer's instructions. The support of hood KH-2 has not been addressed. [Second comment: The structural details have not been added to the drawings. In addition, per the manufacturer's listing information, "Warning: vertically or horizontally lagging hoods to wooden joists, trusses, or studs is an unacceptable method for hanging hoods. This will lead to both structural and thermal failure causing injury and/or death." Support of hood KH-2 was not addressed.] [Initial comment: Include the structural details that show how both of the Type I hoods and the new AC units will be supported from the building structure. Verify with the manufacturer that the method of support is appropriate for hood KH-2. Reference: Section 302.1, IMC 2012.]
06/15/2017 MMENDIB1 WWM REVIEW Needs Review