Permit Number: T17CM02387
Parcel: 10602001C

Address:
3964 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM02387
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Verify that the existing demising wall by hood KH-1 is constructed with non-combustible supports. Reference: Section 507.9, IMC 2012.]
2. The structural details have not been added to the drawings. In addition, per the manufacturer's listing information, "Warning: vertically or horizontally lagging hoods to wooden joists, trusses, or studs is an unacceptable method for hanging hoods. This will lead to both structural and thermal failure causing injury and/or death." Support of hood KH-2 was not addressed. [Initial comment: Include the structural details that show how both of the Type I hoods and the new AC units will be supported from the building structure. Verify with the manufacturer that the method of support is appropriate for hood KH-2. Reference: Section 302.1, IMC 2012.]
3. Comment not addressed. [Initial comment: Provide the listing information for the fryer hood that indicates that it does not have to comply with the requirements of Section 507.12, IMC 2012.]
05/19/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/19/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the discharge from the dishwasher (kitchen equipment number N-922) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012. [Initial comment: Provide the manufacturer's installation requirements for the N-922 dishwasher.]
05/31/2017 MMENDIB1 BUILDING-COMMERCIAL REVIEW Needs Review
05/31/2017 MMENDIB1 WWM REVIEW Needs Review