Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM02387
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | None of the six previous comments were revised.on the drawings. 1. SHEET T1.0; PROJECT GENERAL NOTES: PLEASE COMPLETE THE INFORMATION REQUIRED IN NOTE A. 2. SHEET T1.0; INDEX: THE INDEX INDICATES SHEETS C1, C2, C3, S1, AND S2. THESE SHEETS ARE NOT INCLUDED IN THIS SUBMITTAL. PLEASE PROVIDE. INCLUDE ALL STRUCTURAL DETAILS SHOWN IN CALCULATIONS. 3. SHEET A1.0; FLOOR PLAN; WALL TYPES: FOR THE NEW ONE HOUR FIRE RESISTANCE RATED WALL DESCRIPTION, PLEASE ADD THE U.L. LISTING NUMBER FOR THE 3 5/8" AND THE 6" STUD WALLS. 4. SHEET A1.0; WALL TYPES: FOR ALL NEW WALLS, PLEASE INDICATE THE METAL STUD GAUGE AND SPACING ON THIS SHEET. 5. SHEET A8.0; SECTION 4: FOR THE BRACING AT THE TOP OF THE PARTITION, INCLUDE THE BRACE SIZE AND NUMBER OF CONNECTORS TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE (ROOF STRUCTURE MEMBERS ARE AT 32" O.C. PER THE STRUCTURAL REPORT). 6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/21/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |