Permit Number: T17CM02117
Parcel: 11619226D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM02117
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/29/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify the air balance for the room 303 (Micro) with respect to the supply and exhaust flow rates. Reference: Section 510.5.5, IMC 2012.
2. Confirm the proposed size of the exhaust duct for the fume hood. Reference: Sections 304.1 and 510.5, IMC 2012.
03/30/2017 FRODRIG2 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/04/2017 GERRY KOZIOL WWM REVIEW Completed