Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM02117
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/28/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
03/29/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify the air balance for the room 303 (Micro) with respect to the supply and exhaust flow rates. Reference: Section 510.5.5, IMC 2012. 2. Confirm the proposed size of the exhaust duct for the fume hood. Reference: Sections 304.1 and 510.5, IMC 2012. |
03/30/2017 | FRODRIG2 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
04/04/2017 | GERRY KOZIOL | WWM | REVIEW | Completed |