Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM02117
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/16/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 03/16/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 03/16/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW COMMENT. ALSO PROVIDE A WRITTEN RESPONSE. THE ONE LINE DIAGRAM DOES NOT CORRELATE WITH THE PANEL SCHEDULES AND VOLTAGES AND THE (30 KVA) TRANSFORMER , PANELS 3DPH, 3L1, 3L2. SEE ONE LINE , PLAN SHEET E3.0 |
| 03/17/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 03/17/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 03/17/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/17/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/20/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/20/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/21/2017 | KROBLES1 | WWM | REVIEW | Needs Review |