Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T17CM02103
Parcel: 14027048B

Address:
2825 E GINTER RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM02103
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/28/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/28/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/28/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show the locations of the proposed fire/smoke dampers for FC-3 and FC-4; coordinate with the electrical power design. Flexible ducts shall not penetrate fire partitions. A revision to the plans is required if duct changes are made. [Initial comment: The architect shows fire-rated corridors on sheet A1.0. Clarify how the ductwork will be integrated with the corridors. The ducts from FC-5 that serve the new corridor appear to be running within the corridor enclosure and those from FC-6 appear to be running above the corridor enclosure but there is insufficient information to evaluate how the existing ductwork has been or needs to be modified to accommodate the revised corridors in the southern part of the building. Reference: Section 607, IMC 2012.]