Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM02103
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/28/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/28/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/28/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show the locations of the proposed fire/smoke dampers for FC-3 and FC-4; coordinate with the electrical power design. Flexible ducts shall not penetrate fire partitions. A revision to the plans is required if duct changes are made. [Initial comment: The architect shows fire-rated corridors on sheet A1.0. Clarify how the ductwork will be integrated with the corridors. The ducts from FC-5 that serve the new corridor appear to be running within the corridor enclosure and those from FC-6 appear to be running above the corridor enclosure but there is insufficient information to evaluate how the existing ductwork has been or needs to be modified to accommodate the revised corridors in the southern part of the building. Reference: Section 607, IMC 2012.] |