Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T17CM02103
Parcel: 14027048B

Address:
2825 E GINTER RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM02103
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. The appeal #17-05-01 has been approved by the Building Official. The approval is for 15 total occupants in the warehouse and 35 total occupants in the offices, resulting in a total occupant load of 50 for this building. Please include all of this information in the Code Study on Sheet TS1, including the occupant load analysis and the required exit widths. In addition, include the appeal number, the appeal approval date (7-5-17), and what the appeal was approved for.
07/10/2017 ROBERT SHERRY WATER REVIEW Completed
07/10/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The specified thermostatic mixing valve for the lavatories (Watts L111) is a discontinued product. Specify a currently available product that is listed to ASSE 1070.Reference: Section 607.1.2, IPC 2012.
2. Coordinate the location of the existing drinking fountain in the office area with the architectural drawings (see keynote 10.9 on sheet A1.0).
07/10/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The architect shows fire-rated corridors on sheet A1.0. Clarify how the ductwork will be integrated with the corridors. The ducts from FC-5 that serve the new corridor appear to be running within the corridor enclosure and those from FC-6 appear to be running above the corridor enclosure but there is insufficient information to evaluate how the existing ductwork has been or needs to be modified to accommodate the revised corridors in the southern part of the building. Reference: Section 607, IMC 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
3. Update the background of M1.1 with the current architectural floor plan. Reference; section 107.2.1, IBC 2012.
07/24/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code.
#2. Provide complete compliance with the 2012 IECC for lighting.
#3. Update the expiration date on the electrical registrant stamp.
#4. The new panel designation on the panel schedule does not correlate with the One Line diagram, and floor plans floor plans.
#5. Indicate all conduit, conductor sizes and types for the feeders between the new gutter and CT cabinet.
#6. Provide for a complete grounding electrode system; include grounding electrode conductor sizes and types for the new service as required per 250 NEC.
#7. Show the location of the new service equipment on the power or electrical site plans.
#8. Could not locate Keynote # 9 shown on the lighting floorplans.
#10. Branch circuit and panel designations not shown for some of the luminaires as per keynote #6.
Ref: 2012 IBC sec 107.2.1, 2011 NEC, 2012 IECC, Tucson/Pima County Outdoor Lighting Code.
08/01/2017 GERRY KOZIOL WWM REVIEW Approved SEPTIC APPROVED ON 8/1/17 BY JERRY GODOY.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2017 QJONES1 APPROVAL SHELF Completed
08/25/2017 QJONES1 OUT TO CUSTOMER Completed
08/25/2017 QJONES1 REJECT SHELF Completed