Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM01475
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2017 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/04/2017 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/04/2017 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL All fan coil units in the HVAC cooling load calculations indicate an outside Db summer design temperature other than 104-degrees F which is the required summer design temperature per the City of Tucson per amendment to 2012 IECC. Calculations for all units should indicate the same Db design temperature and program rerun. On the heat pump schedule, sheet M301, cooling sensible capacities for all selected units are in excess of the calculated sensible cooling loads. For example FC-4 shows a calculated sensible load of 8.4 MBH and a sensible capacity of 18.7 MBH for the selected unit. Please justify why the capacity for each unit is in excess of the calculated cooling load. Ref. 2012 IECC C403.2.2. |
| 04/17/2017 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | Smoke Control and Rated Vertical Openings need to be addressed. Approved drawings and will wait for these issues to be corrected. |