Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM00706
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/27/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 01/27/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the control of the exhaust fans in the restrooms so that they operate when the HVAC air is being supplied to the restrooms during ocupied hours. 2. Provide an exhaust fan for the cooking appliances not located under a Type II hood. Reference: Section 507.2.2, IMC 2012. |
| 01/27/2017 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 01/27/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/27/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/27/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/27/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the hot water distribution system so that the hot water source is within 50-feet of the use points. 2. Specify a mixing valve that is listed to ASSE 1070. Install per the manufacturer's instructions. |
| 01/27/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/30/2017 | KROBLES1 | ENGINEERING | REVIEW | Needs Review | |
| 01/30/2017 | GERRY KOZIOL | WWM | REVIEW | Completed |