Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM00140
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/09/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. COMcheck Envelope Compliance form not found with this submittal. [Initial comment: The portion of the building shell being modified in this activity does not appear to have been conditioned. Section C101.4.5, IECC 2012 requires the space to be brought into full compliance with the current energy code as new construction. Provide energy code compliance calculations (e.g. COMcheck) for the building envelope, the mechanical systems, and the interior lighting; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.] 2. Heating and cooling load calculations not found with this submittal. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.] |
| 03/09/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide third-party listing information for the pet bath tub and for the aquarium sink and bagging station. [Initial comment: Provide third-party listing and material standards for all plumbing fixtures being provided by others. Include all proposed fixtures in the Plumbing Fixture Schedule on sheet P1.1. Reference: Sections 303.4 and 402, IPC 2012 and Section 107.2.1, IBC 2012.] |
| 03/09/2017 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Comment not addressed. [Initial comment: Provide the size of the water meter serving this suite. The private utility plan (activity T16CM0863) proposed the installation of a 2" meter and a 2-1/2" reduced pressure backflow prevention assembly located outside of the building near column M-4.6. (Note: it would be helpful if you used the same column numbering system as the architect.) Reference: Section 107.2.1, IBC 2012.] 2. Comment not addressed. [Initial comment: Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (i.e. outside of the building). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf] |
| 03/10/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 2; SHEET A0.1; CODE DATA (EXIT ACCESS TRAVEL DISTANCE): THE REFERENCE TO TABLE 1015.1 HAS NOT BEEN REVISED. 2. PREVIOUS COMMENT 8; SHEET A3.1 (DOOR SCHEDULE): PLEASE PROVIDE ONE SET OF ARCHITECTURAL SPECIFICATIONS TO REVIEW THE DOOR HARDWARE. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/30/2017 | LBOJORQ1 | WWM | REVIEW | Needs Review | |
| 03/30/2017 | LBOJORQ1 | ZONING | REVIEW | Needs Review |