Permit Number: T16CM09446
Parcel: 14041134D

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM09446
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/19/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET PV0.0; PROJECT INFORMATION (ROOF LOADS): IT APPEARS A TYPO. ERROR WAS MADE IN THE FRAMING DEAD LOAD (45 PSF). PLEASE VERIFY.
2. SHEET PV1.30; OVERALL PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CLEAR DIMENSIONS FOR ACCESS PATHS AND CLEARANCES.
3. SHEET PV1.30; OVERALL PLAN: THE NORTH/SOUTH DIMENSIONS FOR MANY OF THE ARRAYS ARE MISSING ON THIS SHEET. PLEASE PROVIDE FOR ALL ARRAYS ON THIS SHEET, OR REFERENCE SHEETS PV1.40 THROUGH PV1.44 FOR THOSE DIMENSIONS.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2017 ARUIZ1 OUT TO CUSTOMER Completed