Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM09446
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/17/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/19/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET PV0.0; PROJECT INFORMATION (ROOF LOADS): IT APPEARS A TYPO. ERROR WAS MADE IN THE FRAMING DEAD LOAD (45 PSF). PLEASE VERIFY. 2. SHEET PV1.30; OVERALL PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CLEAR DIMENSIONS FOR ACCESS PATHS AND CLEARANCES. 3. SHEET PV1.30; OVERALL PLAN: THE NORTH/SOUTH DIMENSIONS FOR MANY OF THE ARRAYS ARE MISSING ON THIS SHEET. PLEASE PROVIDE FOR ALL ARRAYS ON THIS SHEET, OR REFERENCE SHEETS PV1.40 THROUGH PV1.44 FOR THOSE DIMENSIONS. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/24/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |