Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM07611
Parcel: 124050630

Address:
760 N TYNDALL AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM07611
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: T16CM07611
Cup It Up American Grill
Building Plan (1st Review)

TRANSMITTAL DATE: October 18, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. As an outdoor seating area is proposed either provide an approved site plan showing the outdoor seating or a new development package is required.

3. Until the above comment is addressed the building plans cannot be approved.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/28/2016 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Approved
10/28/2016 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change Add R-38 insulation for roof assembly per architectural building sections.

T16CM07611 - PLAN REVIEW COMMENTS
Reviewer: Christopher Anderson, October 26, 2016
BUILDING – COMMERCIAL
On 3/A2.0 Window Elevation, change .70 U-Value to “maximum .50 U-Value” and .35 SHGC to “0.25 SHGC.” Ref. IECC Table C402.3 and COMcheck.
On sheet A2.0 Door Schedule, a deadbolt for door 01 can only be provided for this main exterior door in conjunction with “a readily visible durable sign posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.” Ref. IBC 1008.1.9.3 (2.2).
On sheet A2.0 Door Schedule, a deadbolt is not permitted. Ref. IBC 1008.1.9 and 1008.1.9.4.
On sheets A3.0 - A3.3, keynote 32 refers to pine planks on ½” plywood interior wall finish. However IBC 803.9 requires Class C interior wall finishes for nonsprinklered A-2 occupancies. Per 803.1.1 Class C finishes shall have a flame spread index 76-200, and a smoke-developed index of 0-450. Provide proof that the specified finish complies or that the materials have been tested in accordance with NFPA 286 (exception to 803.1.1).
On sheet S2.1, the new 712 lb kitchen exhaust fan is not shown on the Roof Framing Plan nor are the existing roof rafters evaluated in the structural calculations for adequacy to carry the new load.
10/28/2016 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
OA calculation table indicates that bathroom exhaust fans will be intermittently run. Interlock fans with light switches/occupancy sensors in each room.
Sheets M3.1 – M3.4 are included elsewhere in the drawing set as FS-sheets. What is the reason for the redundancy?

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2016 LBOJORQ1 APPROVAL SHELF Completed
11/10/2016 LBOJORQ1 OUT TO CUSTOMER Completed
11/10/2016 LBOJORQ1 REJECT SHELF Completed