Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM06577
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/01/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/01/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. #1. As per the last electrical plan review, it was requested to provide full compliance with the Tucson Outdoor Lighting Code. The Tucson / Pima County Outdoor Lighting Code can be downloaded from www.tucsonaz.gov/pdsd. Provide all the information in detail as required in sections 104.2, 104.2.1, thru 106 of this code, include this information in the plan documents (Lighting Plans) for approval. Also be advised, lamp color temperature cannot exceed 3500 kelvin per sec. 402.1. Ref: IBC 107.2.1, Tucson / Pima County Outdoor Lighting Code. |