Permit Number: T16CM06577
Parcel: 11202003D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM06577
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/03/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/04/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the location of the cleanouts shown on the storm riser diagram with the plumbing plans and verify that cleanouts are located at the base of each stack and no further than 100-feet apart. (Reference: section 1101.8, IPC 2012.) Include the area drains at the base of the upper ramp when determining the pipe sizes. [Initial comment: Coordinate the storm riser diagram with the plumbing plans and include the area drains for the stair landings. Show drainage areas for the area drains and the roof drain located at DW-7.]
11/04/2016 DAVID RIVERA ZONING REVIEW Approved
11/16/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment.
#1. As per the last electrical plan review, it was requested to provide full compliance with the Tucson Outdoor Lighting Code.
The Tucson / Pima County Outdoor Lighting Code can be downloaded from www.tucsonaz.gov/pdsd. Provide all the information in detail as required in sections 104.2, 104.2.1, thru 106 of this code, include this information in the plan documents (Lighting Plans) for approval. Also be advised, lamp color temperature cannot exceed 3500 kelvin per sec. 402.1.
Ref: IBC 107.2.1, Tucson / Pima County Outdoor Lighting Code.