Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM06535
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2016 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | BUILDING - COMMERCIAL 1. On sheet A-1, "Regulatory Agency Summary" references 2010 ADA - American with Disabilities Act." This notation shall be changed to "IBC Chapter 11 and ANSI A117.1-2003." Reference: IBC 1101.2. 2. On sheet A-1, General Note 3 references ADA and ADAAG. Change text to ANSI A117.1. 3. On sheet A-1, General Note 4 references Scottsdale Fire Code and the ADA. Change text to refer to the 2012 International Fire Code and ANSI A117.1. 4. On sheet -1, General Note 39 specified R-11 insulation for walls and R-19 insulation for roofs. This does not comply with the 2012 IECC Table C402.2. 5. On sheet A-1 "Fire Dept. Notes" do not comply with the City of Tucson requirement that all text (upper and lower case) be at a minimum 3/32" high. 6. On sheet A-1, "Occupancy/Exits" states that 1 exist is required; however the occupant load exceeds 49, therefore 2 exits are required. Reference IBC 1015.1 and Table 1015.1. 7. On sheet A-1, "Occupancy/Exits" state that this facility is "Occupancy A-3, non-separated." Reference: IBC 303.4 and 508.3. 8. On sheet A-2, remove all references to "ADA" in General Notes and Floor Plan Keynotes. 9. On sheet A-2, the exterior door at the northeast side of the north wall shall be an exit door meeting all requirements of IBC Section 1008. 10. On sheet A-2, the distance from the west wall in the accessible women's restroom to the obstructing east wall opposite the entry door must be 54" minimum since the door has a closer per hardware schedule. Reference: ANSI A117.1 Figure 404.2.3.2 (f). 11. On sheet A-2, the distance from the west wall in the accessible men's restroom to the obstructing lavatory opposite the entry door must be 54" minimum since the door has a closer per hardware schedule. Reference: ANSI A117.1 Figure 404.2.3.2 (f). 12. On sheet A-2, the distance from the west wall in the accessible shower room to the obstructing jogged wall opposite the entry door must be 54" minimum since the door has a closer per hardware schedule. Reference: ANSI A117.1 Figure 404.2.3.2 (f). 13. On sheet D-1, wall type K shall be constructed as a fire partition in accordance with IBC Section 708. Since, according to these documents, the building has a fire sprinkler system, the fire-resistance rating shall be minimum 1 hour. 14. On sheet D-3, change callout for last door in Door Schedule to "H". 15. Add entry door (reception) and exit door (studio) to Door Schedule and indicate hardware. |
| 08/30/2016 | CLAYTON TREVILLYAN | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING - COMMERCIAL 1. Per City of Tucson amendment to the 2012 IPC, new section 416.6 lavatory faucets shall dispense a maximum of 0.25 gallon per metering cycle. Revise Plumbing Fixture Schedule to show this. |
| 08/30/2016 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL - COMMERCIAL 1. Electrical sheets are not sealed by the Engineer and are marked "Preliminary - not for construction." Submit sealed documents. 2. On sheet E1, provide exit lights on hallway side over door H and in hallway where hallway terminates at the reception area. 3. On sheet E1, there is an exit light shown over exterior double doors in the studio. The architectural plan indicates that these doors will be blocked with exercise equipment. Relocate this exit light north on ceiling with directional arrow pointing to door A. Provide additional exit light over door A on studio side. |
| 08/30/2016 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL - COMMERCIAL 1. On sheet M-2, note 3 for the Outside Air Calculation says that "outdoor air required to make up restroom exhaust is being provided by outdoor air required for the area being served by the same unit." What is your logic for not interlocking the restroom and shower exhaust fans with the mechanical unit(s) supply fan(s)? 2. The mechanical systems indicated as existing were not part of the previous permit. Provide heating and cooling system information on the construction drawings. 3. Provide heating and cooling load calculations in accordance with the 2012 IECC. |
| 09/08/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | 1. On sheet A-1, General Note 4 references Scottsdale Fire Code. Change text to refer to the 2012 International Fire Code. 2. On sheet A-1 "Fire Dept. Notes" do not comply with the City of Tucson requirement that all text (upper and lower case) be at a minimum 3/32" high. 3. On sheet A-1, "Occupancy/Exits" states that 1 exist is required; however the occupant load exceeds 49, therefore 2 exits are required. Reference IBC 1015.1 and Table 1015.1. 4. Unable to locate exit doors on door schedule, sheet D-3. Indicate how these doors meet requirements of 2012 IFC, section 1008.1.10 |
| 09/21/2016 | ROBERT SHERRY | WATER | REVIEW | Completed |