Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM06462
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/19/2016 | FRODRIG2 | WWM | REVIEW | Completed | |
08/22/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
08/25/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the plumbing code to be used for this activity. The Building Information notes on sheet G001 refer to the 2012 UPC but the calculations on sheet P100 refer to the 2009 IPC. The 2012 International Plumbing Code has been adopted by the City of Tucson and this review has been made using the 2012 IPC. 2. Revise the upper and lower case font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 3. Coordinate the plumbing plans, and the waste and vent diagrams (e.g. see the type and location of the grease interceptor). Reference: Section 107.2.1, IBC 2012. 4. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 5. The total proposed hot water capacity is 8.8 GPM with an 80 degree Fahrenheit rise but the hot water demand appears to be over 17 GPM using Table E103.3(2) and Table E103.3(3), IPC 2012. Show how the proposed hot water capacity will be able to supply the projected hot water demand. Reference: Section 607.1, IPC 2012. 6. Clarify the description for BF-1. The Plumbing Fixture Schedule on sheet P110 specifies the BF-1 as an ASSE 1022-listed dual check valve with an intermediate vent but the Equipment Responsibility schedule on sheet P100 refers to the BF-1 as a double check valve. 7. All water outlets or direct-connection of water to an appliance shall be protected against backflow. Specify the device to be used for each outlet or appliance connection. Reference: Sections 608.15 and 608.16, IPC 2012. 8. The plumbing plans for the shell building included the installation of a backwater valve for the building sewer located within the patio. Show the location of the backwater valve on the 9. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 10. Coordinate the total natural gas demand and longest pipe length values as shown in the Gas Piping Installation Notes (#2) on P220, Key note 2 on sheet P220, the gas piping plan on P220, and the gas isometric detail on sheet P110. |
08/25/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/25/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the upper and lower case font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. The carbon dioxide storage appears to consist of more than two 50-pound cylinders; provide a mechanical exhaust system activated by an asphyxiant gas detection system. Reference: Tucson Fire Department Standard Operating Guideline for Compressed Gases dated 04/28/2015. 3. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2012. 4. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012. 5. Detail 10/M300 shows the specified water heaters installed with the piping below the water heaters having a minimum clearance of 6'-0" above the finished floor. With an overall height of 31.2" and a minimum 6" clearance from the top of the water heaters to combustibles, how will the water heaters be installed in a room with a ceiling height of 9'-0"? 6. Clarify the term "initialize" used in key note 5 on sheet M210: do you mean "start"? Reference: Section 107.2.1, IBC 2012. 7. Provide the dimensions of the grease duct for hood HD-1. Reference: Section 107.2.1, IBC 2012. 8. Identify which of the hoods shown on sheet M410 is to be installed and the hanging weight of the hood. Reference: Section 107.2.1, IBC 2012. 9. Show that the clearances for the Type I hood comply with Section 507.9, IMC 2012. 10. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012. |
09/12/2016 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Reviewer: Chris Anderson, September 9, 2016 BUILDING - COMMERCIAL On sheet A100, add note regarding roof insulation. Is it existing with the shell or added by the contractor as part of this project? Minimum R-38 insulation required per IECC Table C402.2. On Sheet A110, Group 3 hardware used for door 105 specifies a cylinder lock. This is an exit door. No manually operated flushbolts or surface bolts are permitted per IBC 1008.1.9.4. Also, lockset/latchset or panic hardware must be provided that will allow a readily operable door from the inside without using a key or special knowledge per IBC 1008.1.9. On Sheet A200, details D4 and D5 refer to structural for the patio canopy. No structural sheets were included in this drawing set. Submit structural drawings and calculations sealed by an Arizona registrant. |
09/12/2016 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL - COMMERCIAL On lighting plan 1/E100, add directional exit sign at south end of seating area pointing to rear exit door. Exterior elevations on sheet A200 and lighting plan 1/E100 show a “light string” mounted below the outside patio cover. Submit lumen calculations for the entire site with these lamps included per the City of Tucson/Pima County Outdoor Lighting Code. The lighting area for this parcel is E3. On OneLine Diagram 1/E300 add keynotes. I assume that the keyed Notes shown to the right of the diagram pertain to it. |
09/22/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |