Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM05903
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/08/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the size of the gas pipe that drops down in the wall to the cook line; it is 2" on sheet P1 but 1-1/2" on sheet P2. 2. Check the gas loads shown on the gas piping between the water heater branch and the branch serving the rooftop units and also the section of pipe between the gas meter and the water heater branch. 3. At a minimum, beverage dispensers (e.g. espresso dispenser, coffee dispenser, etc.) require the use of a backflow preventer that is listed to ASSE 1022. Reference: Section 608.16.10, IPC 2012. 4. Clarify the drain connections for the three hand sinks, K-1. Two are noted as being connected to "existing sewer" but it is not clear if they are to be connected to the sanitary waste or the grease waste. A third K-1 hand sink is identified on sheet P1 but the sink is not shown on the plumbing plan and no connections (HW, CW, or waste) are shown. 5. Note which kitchen fixtures and appliances require indirect drains and verify that an indirect waste receptor is available for them (e.g. K5, K27, K36, K37, K43, K44, and K48). 6. Verify that the discharge from the ware washer (kitchen equipment number K27) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012. |
08/08/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the specifications for AC-2; the Mechanical Compliance Certificate indicates that it is to be equipped with an economizer but the Packaged Rooftop Unit Schedule does not include an economizer. 2. Provide the listed exhaust flow rate information for the Type I hood that is being used or provide an exhaust flow rate that complies with the requirements of Section 507.13.2, IMC 2012. |
08/09/2016 | ROBERT SHERRY | WATER | REVIEW | Completed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/29/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |