Permit Number: T16CM05419
Parcel: 117120860

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM05419
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2016 ANDREW CONNOR ZONING REVIEW Approved
07/13/2016 LOREN MAKUS ENGINEERING REVIEW Approved
07/14/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/14/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show how the return air from rooms 113 and 114 can reach FC 1-3 without using corridor 115 as a duct.
07/14/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; FLOOR PLAN: PLEASE INDICATE THE ELEVATION REFERENCES (4, 5, 6, AND 7) ON THE PLAN.
2. SHEET A1; TOILET PLAN 3: THE HORIZONTAL GRAB BAR AT THE WATER CLOSET ON THE SIDE WALL IS NOT CALLED OUT IN THE TOILET KEYNOTES. PLEASE VERIFY.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/14/2016 ROBERT SHERRY WATER REVIEW Reqs Change Verify the available water pressure. The data from Tucson Water shows an available water pressure range of 43 to 53 PSI.
07/14/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the pipe sizing calculations based on the available water pressure.
07/14/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/15/2016 MARTIN BROWN FIRE REVIEW Approved