Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM05419
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 07/13/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/14/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/14/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show how the return air from rooms 113 and 114 can reach FC 1-3 without using corridor 115 as a duct. |
| 07/14/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1; FLOOR PLAN: PLEASE INDICATE THE ELEVATION REFERENCES (4, 5, 6, AND 7) ON THE PLAN. 2. SHEET A1; TOILET PLAN 3: THE HORIZONTAL GRAB BAR AT THE WATER CLOSET ON THE SIDE WALL IS NOT CALLED OUT IN THE TOILET KEYNOTES. PLEASE VERIFY. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 07/14/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify the available water pressure. The data from Tucson Water shows an available water pressure range of 43 to 53 PSI. |
| 07/14/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify the pipe sizing calculations based on the available water pressure. |
| 07/14/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/15/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |