Permit Number: T16CM05306
Parcel: 11614163A

Address:
2010 W ANKLAM RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM05306
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2016 MARTIN BROWN FIRE REVIEW Approved
08/03/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS
08/09/2016 ANDREW CONNOR PLANNING-CITY HALL REVIEW Approved
08/09/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
08/09/2016 ANDREW CONNOR ZONING REVIEW Approved
08/16/2016 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the outer circle of the registrant's seal shall be 1-1/2" in diameter, +/- 1/16". The submitted documents have seals with outer circles that are approximately 5/8" in diameter. See Appendix A of the Rules of the Arizona State Board of Technical Registration for further information regarding seals.
3. Provide sealed copies of the structural calculations for the monopalm and its foundation and for the attachment of the antennae for review as noted on sheet C-3.
08/22/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.
1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the outer circle of the registrant's seal shall be 1-1/2" in diameter, +/- 1/16". The submitted documents have seals with outer circles that are approximately 5/8" in diameter. See Appendix A of the Rules of the Arizona State Board of Technical Registration for further information regarding seals.
3. Plans must be legible, fully
dimensioned and drawn to scale with a minimum text size of 3/32" uppercase
or lowercase. This is often an overlooked requirement, however you may be asked to enlarge text size
prior to submitting plans. Per the City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2016 KROBLES1 OUT TO CUSTOMER Completed