| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2017 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T16CM05017 Revision 2 - PLAN REVIEW COMMENTS Reviewer: Chris Anderson, December 11, 2017 BUILDING - COMMERCIAL Sheet A101. Item 21 and other affected sheets: The door between M.A. and Staff Lounge has been changed from a side swinging door to a pocket door. This is an egress door and must be either a side swinging or pivot type. Ref. 2012 IBC 1008.1.2. On Wall Finish Plan, new sheet IWF-1.0, provide smooth, hard, nonabsorbent surface on walls and partition within 2’ of water closet in toilet room 122. Ref. 2012 IBC 1210.2.2. |
| 12/11/2017 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL - COMMERCIAL The electrical sheet backgrounds do not match the revised architectural backgrounds. Revise the electrical sheets showing appropriate changes to electrical (i.e. Instrument Processing Room 224 now has clothes washing machines). |