Permit Number: T16CM03369
Parcel: 129011150

Address:
1050 S PLUMER AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03369
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2016 ANDREW CONNOR ZONING REVIEW Approved
05/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating/cooling load calculations to justify the capacities of the proposed heat pumps.
05/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/05/2016 LOREN MAKUS ENGINEERING REVIEW Approved
05/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S1.0; ROOF FRAMING PLAN: PLAN NOTE 8 INDICATES NEW MECHANICAL TO REPLACE EXISTING UNITS OF EQUAL OR GREATER WEIGHT. PLEASE INDICATE IF THE NEW UNITS ARE HEAVIER THAN THE EXISTING, A STRUCTURAL ANALYSIS FOR THE EXISTING ROOF STRUCTURE IS REQUIRED.
2. SHEET S1.0; SECTIONS A AND B: PLEASE INDICATE THESE SECTION CUTS ON PLAN 2 ON SHEET A2.
3. SHEET P1; DETAIL 2: PLEASE INDICATE THE ANCHOR SIZE AND QUANTITY REQUIRED FOR THE FRAME CONNECTION TO THE EXISTING WALL. WHAT IS THE WALL CONSTRUCTION? INDICATE ADDITIONAL BRACING IN THE EXISTING WALL AS REQUIRED.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/05/2016 ROBERT SHERRY WATER REVIEW Completed
05/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/05/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/06/2016 MARTIN BROWN FIRE REVIEW Reqs Change Sheet A1 indicates an area increase was taken for automatic sprinkler system. We have no record of a sprinkler system in this building or of any required sprinkler inspections. Please clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/10/2016 ARUIZ1 OUT TO CUSTOMER Completed