Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM02951
Parcel: 140420120

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM02951
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/05/2016 ROBERT SHERRY WATER REVIEW Completed
05/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/11/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A.2; FLOOR PLAN: AT DOORS D12 AND D13, IT DOES NOT APPEAR THE MANEUVERING CLEARANCE ON THE PUSH SIDE MEETS THE REQUIREMENTS OF THE ICC/ANSI FIGURE 404.2.3.2(b) AND TABLE 404.2.3.2. PLEASE VERIFY.
2. SHEET A.3; ENLARGED PLAN 1: AT THE URINAL, PLEASE VERIFY THE REQUIREMENT FOR A FORWARD APPROACH PER THE ICC/ANSI FIGURE 305.7(a) IS MET IF THE PARTITION BETWEEN THE URINAL AND THE LAVATORY IS GREATER THAN 24" IN LENGTH.
3. SHEET A.3; WALL TYPES: AT THE BASE OF THE WALLS, PLEASE INDICATE THE RAMSET PIN SIZE.
4. SHEET A.3; WALL TYPES: AT THE TOP OF THE WALLS THAT REQUIRE CROSS BRACING, PLEASE INDICATE THE BRACING SIZE AND SPACING, AND CONNECTORS (SIZE AND QUANTITY) REQUIRED AT THE WALL AND TO THE STRUCTURE ABOVE.
5. SHEET A.4; WAITING AREA ELEVATION: PLEASE VERIFY THE TRANSACTION WINDOW MEETS THE REQUIREMENTS FOR SALES AND SERVICE AREA COUNTERS AS SPECIFIED IN THE ICC/ANSI SECTION 904 FOR ALLOWABLE HEIGHT.
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/18/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide compliance with the 2012 IECC for the interior Lighting. Ref: 2012 IECC.