| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/05/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/05/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/11/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A.2; FLOOR PLAN: AT DOORS D12 AND D13, IT DOES NOT APPEAR THE MANEUVERING CLEARANCE ON THE PUSH SIDE MEETS THE REQUIREMENTS OF THE ICC/ANSI FIGURE 404.2.3.2(b) AND TABLE 404.2.3.2. PLEASE VERIFY. 2. SHEET A.3; ENLARGED PLAN 1: AT THE URINAL, PLEASE VERIFY THE REQUIREMENT FOR A FORWARD APPROACH PER THE ICC/ANSI FIGURE 305.7(a) IS MET IF THE PARTITION BETWEEN THE URINAL AND THE LAVATORY IS GREATER THAN 24" IN LENGTH. 3. SHEET A.3; WALL TYPES: AT THE BASE OF THE WALLS, PLEASE INDICATE THE RAMSET PIN SIZE. 4. SHEET A.3; WALL TYPES: AT THE TOP OF THE WALLS THAT REQUIRE CROSS BRACING, PLEASE INDICATE THE BRACING SIZE AND SPACING, AND CONNECTORS (SIZE AND QUANTITY) REQUIRED AT THE WALL AND TO THE STRUCTURE ABOVE. 5. SHEET A.4; WAITING AREA ELEVATION: PLEASE VERIFY THE TRANSACTION WINDOW MEETS THE REQUIREMENTS FOR SALES AND SERVICE AREA COUNTERS AS SPECIFIED IN THE ICC/ANSI SECTION 904 FOR ALLOWABLE HEIGHT. 6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/18/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide compliance with the 2012 IECC for the interior Lighting. Ref: 2012 IECC. |