Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM02896
Parcel: 127121200

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T16CM02896
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2016 MARTIN BROWN FIRE REVIEW Approved
05/04/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The rim elevation of the next upstream sanitary manhole (8941-05, 2569.6') is less than 12" below the first floor elevation (2570.4'). Provide a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
05/04/2016 ROBERT SHERRY WATER REVIEW Completed
05/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
2. Mechanical General Note #4 on sheet M.1.0 calls for the installation of condensate drains and refers to the plumbing drawings for the sizes, routes, and termination of the drains. Clarify what is to be done with the condensate drains. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
05/09/2016 CPIERCE1 ZONING REVIEW Needs Review
05/09/2016 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
05/09/2016 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/15/2016 CPIERCE1 OUT TO CUSTOMER Completed