Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T16CM02896
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/26/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/04/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The rim elevation of the next upstream sanitary manhole (8941-05, 2569.6') is less than 12" below the first floor elevation (2570.4'). Provide a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. |
05/04/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/05/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 2. Mechanical General Note #4 on sheet M.1.0 calls for the installation of condensate drains and refers to the plumbing drawings for the sizes, routes, and termination of the drains. Clarify what is to be done with the condensate drains. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. |
05/09/2016 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
05/09/2016 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
05/09/2016 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/15/2016 | CPIERCE1 | OUT TO CUSTOMER | Completed |