Permit Number: T16CM02729
Parcel: 112071600

Address:
2543 E GRANT RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T16CM02729
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change 1. Cannot find the hardware Set No.'s that are indicated on the Door Schedule on sheet A6.1. Please indicate which page the Hardware Set No.'s are located.
2. The keynote 1 on sheet A6.1 indicates a "Push Bar" on certain doors. Is this panic or exit hardware? Any other locking devices on these doors?
3. Sheet TS and A1.3 does not indicate that a Fire Alarm System will be installed. Please see Chapter 9 of the IFC and indicate the type of system that will be installed.
4. Sheet TS and A1.3 indicates that only 2 exits are required for the building. The occupant load indicated exceeds 500 and a the minimum required is 3 per IFC 1015.2.
5. Sheet A2.18 is labeled as an Enlarged Building Floor Plan. The submitted set of drawings does not have a floor plan on this page.
6. Please provide a seating plan for all Assembly Areas so I can determine compliance with Section 1028 of the IFC.
05/03/2016 ROBERT SHERRY WATER REVIEW Completed
05/09/2016 LOREN MAKUS ENGINEERING REVIEW Approved
05/09/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principal Planner

PROJECT: The Yard - 2543 E. Grant Road
T16CM02729
Building Plan (1st Review)

TRANSMITTAL DATE: May 9, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plan for compliance to development package DP15-0190 and it appears the plans meet the requirements but Zoning will not approve the building plans until all other PDSD review agencies have approved the building plans.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/16/2016 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
07/06/2016 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/06/2016 FERNE RODRIGUEZ OUT TO CUSTOMER Completed