Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T16CM02662
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 04/12/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Describe the mechanical and air conditioning modifications mentioned in the violation notice. |
| 04/12/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide circuit and panel designations on the floor plans for the new receptacles. Ref: IBC 107.2.1, NEC art. 408. |
| 04/12/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/12/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. GENERAL: IF THIS IS FOR A CERTIFICATE OF OCCUPANCY, A FULL CODE ANALYSIS WILL BE REQUIRED FOR EGRESS, PLUMBING FIXTURES, ACCESSIBILITY, ETC. PLEASE VERIFY. 2. GENERAL: IF THIS IS FOR A LETTER OF COMPLETION, THE PROVIDED INFORMATION IS SUFFICIENT. 3. GENERAL: PLEASE PROVIDE A WALL DETAIL(S) FOR THE NEW INTERIOR PARTITION. INCLUDE STUD SIZE AND SPACING, CONNECTION AT FLOOR SLAB, CONNECTION/BRACING OF THE TOP OF THE PARTITION TO THE STRUCTURE ABOVE. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/12/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/12/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Describe the plumbing modifications mentioned in the violation notice. |
| 04/12/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/12/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |