Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM01968
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The COMcheck Mechanical Compliance Certificate states, "System Compliance Fails: Economizer requirements have not been met." [Initial comment: Show that the proposed HVAC systems meet the requirements of Sections C403.2 and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.] |