Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM01968
Parcel: 11310001A

Address:
1545 E COPPER ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01968
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2016 MARTIN BROWN FIRE REVIEW Approved
04/14/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/14/2016 ROBERT SHERRY WATER REVIEW Completed
04/14/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/14/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.
2. Specify the required U-factors and Solar Heat Gain Coefficients (SHGC) for the fenestration and doors on the architectural drawings. Reference: Section C103.2, IECC 2012.
3. Show that the proposed HVAC systems meet the requirements of Sections C403.2 and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
04/25/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2016 KROBLES1 OUT TO CUSTOMER Completed