Permit Number: T16CM01930
Parcel: 14041134D

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM01930
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1. Provide complete panel schedules for all panels as required per City of Tucson Commercial Plan Submittal Requirements. Include available fault current, and AIC ratings for the panels. City of Tucson Plan Submittal Requirements can be downloaded from www.tucsonaz.gov/pdsd.
#2. Provide additional information for the load centers and control cabinets such as equipment type or description. For example, are the blocks shown on the one line diagrams identified as " CC " junction boxes, termination cabinets ? And the blocks shown with overcurrent devices identified with a " P " breaker panels ? Loadcenters ?
Ref: IBC sec 107.2.1, NEC ,

Final Status

Task End Date Reviewer's Name Type of Review Description
04/12/2016 ARUIZ1 OUT TO CUSTOMER Completed