Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM01721
Parcel: 12416017A

Address:
602 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01721
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the water pressure used in the water pressure calculations with Tucson Water. Sizing pipes for water distribution systems using Appendix A, UPC 2012 is an accepted engineering method but the average daily minimum pressure is to be used for the calculations. If the average daily minimum water pressure is 80 PSI, provide a pressure reducing valve to limit the maximum water pressure to less than 80 PSI. Reference: Section 604.8, IPC 2012 and Section A 3.3, UPC 2012.
03/21/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide auxiliary drain pans or secondary drain systems for the fan coil units. Reference: Section 307.2.3 IMC 2012.
2. Revise the mechanical design as required to avoid using corridor 142, as a return air duct. Reference: Section 601.2, IMC 2012.
3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
03/31/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T2; CODE CHECK (MEANS OF EGRESS): THE EXIT WIDTH IS DETERMINED USING 332 OCCUPANTS. WHERE DID THAT NUMBER COME FROM (OCCUPANT LOAD CALCULATION INDICATES 463 TOTAL OCCUPANTS)?
2. SHEET T2; CODE CHECK: INCLUDE ON THIS SHEET SECTION 707 (ENERGY CONSERVATION) AND THE REQUIREMENTS.
3. SHEET T2; CODE CHECK (804.4): THE CODE CHECK ON THIS SHEET INDICATES FIRE ALARM AND DETECTION ARE NOT REQUIRED. THE CODE SECTION 804.4 INDICATES 'WHERE AUTOMATIC SPRINKLER PROTECTION IS PROVIDED IN ACCORDANCE WITH SECTION 804.2 AND IS CONNECTED TO THE BUILDING FIRE ALARM SYSTEM, AUTOMATIC HEAT DETECTION SHALL NOT BE REQUIRED'. A FIRE ALARM SYSTEM IS STILL REQUIRED. PLEASE VERIFY.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/04/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved