Permit Number: T16CM01171
Parcel: 13213087F

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM01171
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/01/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Explain why the calculated cooling loads do not agree with the scheduled capacities of the roof top units (with the exception of RTU-2, RTU-3, and RTU-4). [Second comment: Comment not addressed.] [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.]
2. Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. [Second comment: Comment not addressed.] [Initial comment: Show the size, routing, and termination of the condensate drains for the rooftop units. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.]
06/01/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/01/2016 ROBERT SHERRY WATER REVIEW Completed