Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T16CM01171
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/01/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/01/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Explain why the calculated cooling loads do not agree with the scheduled capacities of the roof top units (with the exception of RTU-2, RTU-3, and RTU-4). [Second comment: Comment not addressed.] [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.] 2. Condensate drains shall be terminated at an approved disposal location. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. [Second comment: Comment not addressed.] [Initial comment: Show the size, routing, and termination of the condensate drains for the rooftop units. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.] |
06/01/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
06/01/2016 | ROBERT SHERRY | WATER | REVIEW | Completed |