Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM01171
Parcel: 13213087F

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T16CM01171
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2016 MARTIN BROWN FIRE REVIEW Approved
02/26/2016 ROBERT SHERRY WATER REVIEW Reqs Change Provide the civil site plans that show the location and size of the water service meter, the reduced pressure backflow preventer, and the size and route of the water service pipe to the building. Reference: Section 107.2.1, IBC 2012.
02/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the proposed HVAC system meets the requirements of Sections C403.2, C403.3. Reference: Section C303.1, International Energy Conservation Code 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
3. Verify that the installer setup menu for the specified programmable thermostat includes off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
4. Verify that the hot gas bypass feature of the specified rooftop units complies with the requirements of Section C403.4.7, IECC 2012.
5. Show the size, routing, and termination of the condensate drains for the rooftop units. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
02/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the civil site plans that show the size and route of the building sewer from the building to the junction with the private sewer collection system. Reference: Section 107.2.1, IBC 2012.
2. Provide a cleanout at the base of each vertical rainwater conductor that is connected to an underground storm drain. Reference: Sections 708.3.4 and 101.8, IPC 2012.
3. Show the size, slopes, routing, and termination points for the roof drain and overflow roof drain leaders. Five 4" primary roof drains are shown on the architectural roof plan but the plumbing plan shows three 12" storm drains. None of the other drawings show how they are connected in the building or how they are to be extended to the site storm drain. Five 4" secondary roof drains are also shown on the architectural roof plan but no information regarding the size, route or termination points of their drain leaders are shown. The secondary roof drains shall not terminate below grade but must discharge above grade in a location that is visible to the building occupants or maintenance personnel. Reference: Sections 1106 and 1108, IPC 2012.
03/07/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/17/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T1.01; DRAWING INDEX: PLEASE REVISE THE SHEET NUMBER T1.0 IN THE INDEX.
2. SHEET T1.01; CODE INFORMATION: REMOVE THE 2010 ADAAG FROM THE ACCESSIBILITY CODE.
3. SHEET T1.01; CODE INFORMATION: PLEASE REVISE THE ENERGY CODE TO THE 2012 EDITION OF THE IECC.
4. SHEET T1.01; CODE INFORMATION: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE EXIT CAPACITY PROVIDED.
5. SHEET S0.1; GENERAL NOTES (FOUNDATION): A GEOTECHNICAL REPORT WAS USED FOR THE FOUNDATION DESIGN. PLEASE PROVIDE ONE REPORT FOR REVIEW.
6. SHEET S1.2 (PLAN); STRUCTURAL CALCULATIONS: WERE THE TRASH ENCLOSURE WALLS AND FOOTINGS INCLUDED IN THE STRUCTURAL CALCULATIONS? PLEASE VERIFY AND PROVIDE AS REQUIRED.
7. SHEET S1.2; PLAN: A WALL DETAIL CUT ON THE PLAN INDICATES 4/DTL. 2. PLEASE REVISE TO 2/S1.2.
8. SHEET S1.2; DETAIL 2: PLEASE INDICATE THE WALL VERTICALS ARE #5 @ 24", OR ADD A NOTE TO MATCH THE FOUNDATION DOWELS.
9. SHEET S2.1; FRAMING PLAN: AT THE FUTURE ROOF CANOPY, A SECTION 09/S4.1 IS CUT. PLEASE REVISE THE SECTION REFERENCE.
10. SHEET S4.2; DETAILS 2, 3, AND 4: PLEASE INDICATE ON THE DETAILS THE MINIMUM REQUIRED LENGTH OF WELD REQUIRED AT THE TUBE/PLATE CONNECTION TO MEET THE CALCULATION ANALYSIS.
11. SHEET A1.01 (FLOOR PLAN); KEYED NOTES: NOTE 5 INDICATES A CANOPY ROOF. IF THIS IS A FUTURE CANOPY (PER KEYED NOTE 4 ON SHEET S2.1), PLEASE INDICATE IN NOTE 5 AND ON THE VARIOUS PLANS, DETAILS, SECTIONS AND NOTES WITHIN THIS SET.
12. SHEET A1.01 (FLOOR PLAN); SHEET A7.01 (ENLARGED PLAN 08): IT APPEARS THE STRUCTURAL DRAWINGS CONSIDER THE CANOPY A FUTURE PROJECT, WHILE THE ARCHITECTURAL DRAWINGS DO NOT. PLEASE CLARIFY.
13. SHEET A6.02; WALL SECTION 03: AN ENLARGED DETAIL AT THE TOP OF THE WALL REFERENCES 01/A6.01. PLEASE REVISE THE REFERENCE NUMBER.
14. SHEET A6.02; WALL SECTION 05: AN ENLARGED DETAIL AT THE BOTTOM OF THE WALL REFERENCES 05/A7.02. PLEASE REVISE THE REFERENCE NUMBER.
15. SHEET A6.03; WALL SECTIONS 02 AND 03: AN ENLARGED DETAIL AT THE LOW ROOF REFERENCES 01/A7.03. PLEASE REVISE THE REFERENCE NUMBER.
16. SHEETS A9.01 AND 9.02: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE SCHEDULES.
17. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/21/2016 STEVE SHIELDS ZONING REVIEW Approved
03/21/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code.
#2. Provide for a Concrete Encased Grounding Electrode ( UFER ), include Grounding Electrode Conductor size and type.
Ref: IBC 107.2.1 2011 NEC art. 250.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2016 KROBLES1 OUT TO CUSTOMER Completed