| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/18/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET T1; DEVELOPMENT DATA: IS THIS BUILDING SPRINKLERED? PLEASE ADD A NOTE TO THIS SHEET. 2. SHEET T1; DEVELOPMENT DATA: IF THIS SPACE IS NOT SPRINKLERED, THERE IS AN ISSUE WITH A DEAD END CORRIDOR LENGTH (ALONG GRID 15). PLEASE VERIFY. 3. SHEET A1; INTERIOR WALL 2: FOR THIS ONE HOUR RATED WALL, PLEASE PROVIDE A U.L. NUMBER ON THE DRAWING. 4. SHEET A1; INTERIOR WALL 3: PLEASE INDICATE ON THE DETAIL THE STUD BRACE SIZE AND IT'S CONNECTION TO THE NEW PARTITION WALL AND TO THE STRUCTURE ABOVE. 5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/18/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Cover sheet indicates installation of a med gas system. Please indicate type and quantities of gasses and how stored. Refer to chapter 50 of the 2012 IFC and requirements for hazardous materials. Need details about methods of storing bottles. |
| 02/23/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012. 2. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012. 3. Provide specifications and installation instructions for the two types of hair traps shown on the waste and vent diagram. Reference: Section 303 and 1002.1, IPC 2012. |
| 02/23/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |