Plan Number: T15PI00003
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T15PI00003
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2015 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Denied Submit utility letters as soon as possible.
02/19/2015 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied Submit utility letters as soon as possible.
03/04/2015 GARY WITTWER DOT LANDSCAPE REVIEW Denied 1. Submit a copy of the approved NPPO plan
2. Submit the Landscape and Irrigation plans

Note: private irrigation lines can not be placed under public streets.
03/25/2015 JOSE ORTIZ DOT TRAFFIC REVIEW Reqs Change March 5, 2015


SUBJECT: Robb Hill
PIA Plan I-2015-001, DSD Activity TT15PI00003

PROJECT REVIEWER: Zelin Canchola,
DOT Review Section


RESUBMITTAL REQUIRED: DOT Review Section has reviewed the PIA Plan for Traffic Engineering. Resubmit with the following redlines on sheet 8 of 8.

1. Add skip lines for bike lane at the taper, WG (2x6), and WG8 (2x6)

2. Add "ONLY" marking to deceleration lane.

3. Bike lanes require a minimum of 5 feet. Change 4 feet to 5 feet.

4. For Street name sign add note "Submit shop drawing to Traffic Engineering for approval before fabricating street name signs. Contact Traffic Engineering at 791-4259 for information.



If you have any questions I can be reached at 837-6659 or zelin.canchola@tucsonaz.gov
03/25/2015 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
04/06/2015 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
04/06/2015 LINZUNZA DOT ENGINEERING REVIEW Denied Date: April 3, 2015
PIA Project: Rob Hills, lots 1-53 & Common area A-1, B-1, C-1 & C2
PIA No.: T15PI00003 Plan No. I-2015-001
Project Reviewer: E. Craig Saltzman, Engineering Review Unit


RESUBMITTAL REQUIRED: DOT Review Section has reviewed the PIA Plan for Engineering. Resubmit with the following:

1. Demonstrate existing storm sewer ( CB8 and CB10 sump condition) located in Speedway Blvd. can handle the flows, likewise the pavement spread

2. Verify pavement structural section design for the onsite streets.

3. Structural pavement section within Speedway Blvd. match existing structural pavement section. Reference: Plan Speedway Blvd., Pantano Road to Camino Seco I-83-20 , sht. 2 of 85 AS-Builts Change Order no. 5 (1 ½"Mix #3 on 3 ½" Mix #1 on 6" ABC on 6" Compacted Subgrade)

If you have any questions I can be reached at 837-6621 or craig.saltzman@tucsonaz.gov
04/06/2015 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Denied Submit utility letters as soon as possible.
04/06/2015 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed
04/06/2015 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Denied Submit utility letters as soon as possible.
04/06/2015 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied Submit utility letters as soon as possible.
04/06/2015 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Denied Submit utility letters as soon as possible.
04/06/2015 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Denied Submit utility letters as soon as possible.
04/06/2015 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Denied Submit utility letters as soon as possible.
04/06/2015 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Denied Submit utility letters as soon as possible.