Permit Number: T15OT01478
Parcel: 205640620

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T15OT01478
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2015 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change DATE: November 25, 2015
DUE DATE: December 2, 2015
SUBJECT: Mountain Vail Estates, Part G Floodplain Use Permit
TO: Warren D. Thompson, PE
LOCATION: 11311 E Mary Ann Cleveland
REVIEWERS: Paul Baughman, PE, CFM
ACTIVITY: T15OT01478
SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Floodplain Use Permit. The following items need to be addressed:
1) Per AM 2.06.4.9N6 please add the 100 year water surface elevations to sheet 14 to show water surface elevations upstream of each lot.
2) The drainage report is addressed to Jason Green. He is not reviewing plans at the City of Tucson. Please remove references to his review. If he approved a previous drainage report, please submit a copy as reference with your next submittal. Alternatively, a new drainage report will be required for review and approval.
3) Reference is made to a submittal of drainage information to Laith Alsami. It is not clear from the drainage report if he approved any drainage information. Please provide evidence of his approval with the next submittal. Please remove reference to any previous submittal if approval was not received.
4) Per AM 2-06.4.8G please provide a detail of the flood/retaining wall called out by keynote 21 on sheet 14.
5) Per TSM Section 4-04 please provide scour calculations in accordance with equation 6.3 and section 6.9 of the City of Tucson Drainage Standards Manual to provide for a minimum scour protection for the flood/retaining wall.
6) Per AM 2-06.4.8I and AM 2-06.4.9O please show where locally regulated floodplain limits will be located based on developed conditions. Please also show where FEMA floodplain limits will be based on LOMR submittal. All of the existing and developed conditions FEMA and locally regulated floodplain line work should be reflected in the legend.
7) Please initiate process with City to set up any agreements that may be required based on CFR 44 Sec 65.2 and 65.10 maintenance requirements.
If you have any comments questions or wish to discuss new information, please call or email me at 520-837-5007 or paul.baughman@tucsonaz.gov.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2015 KROBLES1 OUT TO CUSTOMER Completed