Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM08230
Parcel: 140420120

Address:
7005 S PLUMER AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T15CM08230
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2018 QJONES1 APPROVAL SHELF Completed
04/23/2018 QJONES1 OUT TO CUSTOMER Completed
04/23/2018 QJONES1 REJECT SHELF Completed